DL100 Series Universal Low-Power Inverter
58 Detailed Description of Functions
0Upper limit frequency
1 Frequency channel setting value
This parameter is set as the upper limit frequency of PID adjustment, which is
the percentage of the maximum value of PID output corresponding to the
reference reference frequency.
If the feedback value of the system is less than the lower limit of the
disconnection detection, it is considered that it may be in a disconnection state and
the disconnection is detected. After the delay time, the system is still in the
disconnection state, and it is considered that a disconnection fault has occurred.
When the error is within this range, PID will not adjust.
F7.12 Lower limit of disconnection detection
Predetermined area
0.0 ~50.0%
F7.13 Disconnection detection delay time
Predetermined area
0.01 ~60.00Sec
F7.11 PID frequency adjustment reference Predetermined area
0 ~1
F7.14 Static deviation range Predetermined area
0 ~10.0%