1-2
The Simplex 4100 Fire Alarm Control Panel (FACP) has three general functions.
It monitors fire alarm initiating points (smoke detectors, heat detectors, and pull stations).
It activates fire alarm notification appliances (horns, strobes, audio evacuation messages)
when an initiating point activates.
It monitors and controls auxiliary building equipment (fan dampers, relays, security devices).
Note: The term point is used extensively throughout this manual. It is a generic term
used to refer to an individual component of the system, such as a single smoke
detector, a single pull station, etc.)
The 4100 operator interface, shown in Figure 1-1, allows a system operator to control and monitor
the facility-specific components connected to the 4100 FACP.
Figure 1-1. Operator Interface
Table 1-1. Components of the Operator Interface
LED/Key Description Refer To
Fire Alarm LED and Fire
Alarm ACK Key
The Fire Alarm LED flashes to indicate
the presence of an unacknowledged
alarm condition. Other components of
the system, such as the horns and
strobes, also activate to indicate the
presence of an alarm. The FIRE
ALARM ACK key allows you to indicate
that you have observed the presence
of an alarm.
Chapter 2
Alarm Silenced LED/Alarm
Silence Key
Pressing the ALARM SILENCE key
provides a means of silencing the
building’s audible notification
appliances (horns). The LED indicates
when this key has been used.
Chapter 2
Continued on next page
Basic System Description
Overview
Facility-Specific
Control Keys
Labels shown are
examples.
Entry
Keypad
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485

Related product manuals