8-8
1. Press the All Speakers Evac button to play the evacuation message on every speaker circuit
connected to the audio system.
To indicate that the All Speakers Evac function has been activated, the LED associated with
this button illuminates, as do the LEDs for each of the speaker circuits (floors).
Specific floors in the building can be manually evacuated at any time, even when no fire alarm
condition is present. To do this, follow these steps.
1. Press the speaker circuit buttons corresponding to the speaker groups (floors) you want to
evacuate. The LEDs corresponding to the selected speaker groups illuminate.
2. Press the Selective Evac button. The LED associated with the Selective Evac button
illuminates and the Primary Evacuation message plays on the selected speaker circuit.
Example To evacuate floors 1 and 2, you would first press the buttons labeled Floor 1 and
Floor 2. Their LEDs light to let you know that these are the selected floors. Next,
press the Selective Evac button. The Selective Evac LED lights and the message
plays on the selected floors.
When a fire alarm occurs, the evacuation message automatically plays on specific floors but other
floors (or areas) of the building may not automatically play the message. Additional floors can be
evacuated, as follows:
1. Press the speaker circuit button(s) for the additional floors. When you do this, the LEDs for
the selected floors illuminate and the message automatically plays on the speaker circuits for
those floors.
Note: The evacuation message begins at whatever point it is currently at. For example, the
entire message may be, “Please evacuate this Floor. Proceed to your designated assembly
area.” If you press the speaker circuit when the message is half through, only the second half
of the message will play on the additional speaker circuit.
Follow these steps to play the Alert message on specific floors (areas) of the building.
1. Press the speaker circuit buttons corresponding to the speaker groups (floors) on which you
want to play the Alert message. The LEDs corresponding to the selected speaker groups
illuminate.
2. Press the Selective Alert button. The LED associated with the Selective Alert button
illuminates and the Alert message plays on the selected speaker circuit.
Continued on next page
Two Channel Audio Operation, Continued
Evacuate Entire
Building
Evacuate Specific
Floors when No
Alarms are Present
Evacuate Additional
Floors During an
Alarm
Alert Specific Floors
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485