2-8
If a device remains in alarm and no alarm condition (i.e., smoke or an activated pull station) exists,
the 4100 provides a way to inhibit alarm reporting for the malfunctioning point. Disabling a point
causes a trouble condition for the point or zone that you disable.
The <DISABLE> key, which is used to disable points, may be passcode protected. If it is, you
need to first log in to the system using the passcode that enables the key. Refer to “Logging In
and Out of the System” in Chapter 1 for information on doing this.
Be aware of the following issues related to disabling points.
Disabling a point causes the point to NOT report alarm conditions or other status changes. A
point should not be disabled unless it is clearly understood that fire detection or security for
the area of the building covered by that point will be lost. Appropriate steps must be taken to
provide alternate means of protecting the area of the building covered by the disabled point.
If the Service Reset option is enabled, an operator can clear an alarm condition (i.e.,
successfully perform a system reset) even though the device that caused the alarm remains in
a trouble state. The typical application for this would be the case where a malfunctioning
initiating device such as a smoke detector (consisting of a base and removable sensor) causes
an alarm and activates the city circuit. With this option enabled, the sensor can be removed
and the system (including the city circuit) can be reset. Without this option enabled,
removing the sensor would cause a trouble, which would prevent the city circuit from being
reset.
Note: Service Reset is not a UL-Approved option and enabling this option on the
panel invalidates the panel’s UL certification.
To disable a point in alarm, follow these steps.
1. Press the <ALARM ACK> key to display the point’s information on the alphanumeric
display. For example:
2. Press the <DISABLE> key. The alphanumeric display shows the following message.
Note: XX represents the point to be disabled.
Continued on next page
Disabling a Point that Remains in Alarm
Overview
Important Notes
Procedure
SECOND FLOOR EAST WING ROOM 16
PULL STATION ALARM
PRESS <ENTER> TO DISABLE
MONITOR ZONE: ZNXX
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485

Related product manuals