4-4
Acknowledging Supervisory Conditions, continued
Invidivually
Acknowleding
Supervisory
Conditions
If individual acknowledge is enabled on your system, you need to separately acknowledge each
supervisory condition. Use the following procedure to do this.
1. Unlock and open the enclosure door. The display shows the supervisory condition, similar to
Figure 4-1.
2. Press the SUPV ACK key. Repeat this step and read the reports. The display shows the area
and type of condition. The tone-alert silences and the yellow LED glows steady.
3. Read the display. Investigate the problem to determine its cause.
When the problem causing the condition is corrected, the SUPERVISORY LED flashes and the
tone-alert sounds steady.
4. Press the SUPV ACK key. The display shows the system status.
5. Press the SUPV ACK key again. After a short delay, the display indicates that the system is
normal.
firealarmresources.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex InfoAlarm 4100U and is the answer not in the manual?

Simplex InfoAlarm 4100U Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
User InterfaceKeypad and LCD
TypeAddressable Fire Alarm Control Panel
Operating Voltage24 VDC
CommunicationEthernet (optional)
CompatibilitySimplex devices
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing