2-6
Acknowledging an Alarm, continued
Globally
Acknowledging
Alarms
2. Press the ALARM ACK key. Read and follow the instructions on the display. After you press
the ALARM ACK key, the system responds as follows
The tone-alert silences, and the display reports pertinent information about the alarm, such
as:
Figure 2-8. Alarm List
The SYSTEM ALARM LED changes from flashing to steady ON, and all alarm condi-
tions are acknowledged.
Press the ALARM ACK key or the “Prev/Next” keys to scroll to the next alarm. Continue
to do this to review all alarms in the system.
Individually
Acknowledging
Alarms
Use the following procedure if the Individual Acknowledge option is enabled on your FACP
system.
1. Unlock and open the enclosure door. Read the display on the interface panel. It reports the
number of alarm conditions at the bottom of the screen as shown below.
.
Figure 2-9. Bottom of LCD
2. Press the ALARM ACK key. Read and follow the instructions on the display. Refer to
Figure 2-8.
3. Press the ALARM ACK key again. Repeat this procedure to review all reports. Reports are
displayed in chronological order. All unacknowledged alarms flash. The flashing stops once
the alarm has been acknowledged. Press the previous/next keys to scroll through the alarm list.
Tone-alert silences when the last unacknowledged alarm is acknowledged.
System Alarm LED is ON, but no longer flashes.
firealarmresources.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex InfoAlarm 4100U and is the answer not in the manual?

Simplex InfoAlarm 4100U Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
User InterfaceKeypad and LCD
TypeAddressable Fire Alarm Control Panel
Operating Voltage24 VDC
CommunicationEthernet (optional)
CompatibilitySimplex devices
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing