Y070.301/EN Page 11
Operation instructions
SIPOS SEVEN ECOTRON
3
Assembly and connection
3 Assembly and connection
3�2 Electrical connection
The components are designed as to ensure that once connected correctly, uninsulated, live parts
cannot be touched directly; i.e. protection against electric shock is provided in accordance with
IP2X or IPXXB.
Dangerous voltages are also applied when the motor is at standstill. Before opening the terminal
cover or the connection hood, disconnect the supply voltage from the actuator.
Allow at least 1 minute for the capacitors to discharge and do not touch any contacts.
The supply voltage must always lie within the voltage range specied on the name plate.
For short-circuit protection and for disconnecting the actuator from the mains, fuses and
disconnect switches have to be provided by the customer.
Mains cable: Use metal cable glands for mains connection.
Signal cable: Use metal cable glands with cable shielding for the connection of the signal cable
to avoid the occurrence of electronic faults. The signal cable must be shielded and the shield
must be xed or grounded on both sides. Ensure careful connection of the screen within the
cable gland!
It must be ensured that the cable glands and seals (O-rings) are tted carefully and cor-
rectly in order to guarantee the enclosure protection. For details of the permissible conductor
cross-sections, see wiring diagram.
Cable glands and cables are not included in the scope of delivery.
3�2�1 Connection with round plug
1. Unscrew connection hood (g. item 2) with
plug element (1).
2. Unscrew screw plugs from the required cable
entries in the connection hood.
3. Unscrew plug element (1) from connection
hood (2).
4. Screw in the cable gland (3) only slightly and
insert the connecting cables (4).
5. Connect the connecting cables in accordance
with the circuit diagram enclosed in the con-
nection hood, connecting the earth lead to the
provided terminal in the connection box.
6. Screw plug element (1) into the connection
hood (2) and then x connection hood.
7. Tighten cable glands (3).
Fig�: Connection with round plug

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SIPOS Seven Aktorik Ecotron Series and is the answer not in the manual?

SIPOS Seven Aktorik Ecotron Series Specifications

General IconGeneral
BrandSIPOS
ModelSeven Aktorik Ecotron Series
CategoryController
LanguageEnglish

Related product manuals