Chapter: 2 Operation
Alarm Settings
The GDS102 alarm includes shallow water alarm.
An alarm system may be connected to the GDS102 by NMEA com port and/or the relay contacts.
There are 3 available alarm denitions ALF, ALR(A) and ALR(B) set in “Screen 13”
The default is ALF wich is complient with IEC62288 2014.
Shallow water alarm.
Shallow water settings are performed from screen 1. Alarm limits are referred to the indicated depth.
ALF
Active Alert :
SDALF,1,1,0,102103.00,A,A,V,,230,1,<1-99>,0,Shallow alarm*hh
3 beeps every 7-10 seconds, Alert text on screen ‘ashing red’
SDALC,01,01,00,0,,230,1,<1-99>
Active Alert - silenced:
SDALF,1,1,0,102103.00,A,A,S,,230,1,<1-99>,0,Shallow alarm*hh
Internal buzzer silenced for 30 seconds, Alert text on screen ‘ashing red’
SDALC,01,01,00,0,,230,1,<1-99>
Reply after local acknowledge:
SDALF,1,1,0,102103.00,A,A,A,,230,1,<1-99>,0,Shallow alarm*hh
no beep <1-99> counts for each new occurrence of the alarm , Alert text on screen ‘constant red’
SDALC,01,01,00,0,,230,1,<1-99>
Out of Active state unacknowledged: :
SDALF,1,1,0,102103.00,A,A,U,,230,1,<1-99>,0,Shallow alarm*hh
Alert text on screen ‘ashing red’
SDALC,01,01,00,0,,230,1,<1-99>
Out of Active state acknowledged (normal): :
SDALF,1,1,0,102103.00,A,A,N,,230,1,<1-99>,0,Shallow alarm*hh
Alert text on screen ‘black or disappear’
SDALC,01,01,00,0,,,,<1-99>
Responsbility transfer is not accepted.
Illegal sentences will not receive a response (ARC)