SMA Solar Technology AG Connecting External Sources
Technical Description SI5048-TB-TEN110340 117
Generator Interface "234.07 GnStrMod" = Autostart; Generator Request Via
Sunny Island
Generator Interface "234.07 GnStrMod" = GenMan; Generator Request Via
Sunny Island
1 Generator started by Sunny Island
2 Generator start
3 Beginning of warm up time
4 Warm-up time has expired
5 Generator is connected
6Current limit
7 Minimum running time is expired
8 Current is reduced, battery absorption phase
9 Charging process is completed, generator disconnection
10 Generator follow-up time expired, generator disconnection
11 Stop time has expired
1 Generator start by Sunny Island using GenMan
2 Generator start by GenMan
3 Beginning of GenMan warm up time
4 GenMan warm-up time has expired, connection signaled by
GenMan at Sunny Island
5 Sunny Island connects generator
6Current limit
7 Minimum run time (Sunny Island) has expired
8 Current is reduced, battery absorption phase
9 Charge process complete, generator disconnected by Sunny
Island
10 Signal at GenMan
11 GenMan follow-up time has expired, generator stopped
12 Stop time has expired
Power-Dependent Generator Start
Warm up times, minimum run times and follow-up times are also maintained for power
dependent generator starts.