SMA Solar Technology AG Troubleshooting
Technical Description SI5048-TB-TEN110340 215
Interrupt the emergency charge mode, e.g., in order to refill diesel:
1. Press <Enter> to stop the Sunny Island.
☑ The notification shown here is displayed.
2. Press and hold <ENTER>.
☑ The remaining time is displayed as a bar.
☑ The emergency charging mode is interrupted. The
notification shown here is displayed.
In emergency charge mode, process values are shown in the display. Parameters cannot be changed
during the charging process. If the device is restarted, the settings that were saved before the ECM
are loaded.
Prematurely ending the Emergency Charge Mode
In order to exit the emergency charge mode early, the Sunny Island must be restarted with
the "510.01 InvRs" parameter.
Bridge between AC1 and AC2
After emergency charge mode has been completed make sure to remove the bridge
between AC1 and AC2!
Restarting
Observe information for restarting and wait for five minutes (see also section
9.5”Reactivating the Device Following Automatic Shutdown” (page64)).