SMA Solar Technology AG Initial Start-up
Technical Description SI5048-TB-TEN110340 59
GenGrid:
– Maximum generator current (0 A - 224 A), default setting: "16 A"
– Generator interface (Manual, GenMan, Autostart), default setting: "Autostart"
– Maximum grid current (0 A - 224 A), default setting: "16 A"
Grid:
– Maximum grid current (0 A - 224 A), default setting: "16 A"
Gen:
– Maximum generator current (0 A - 224 A), default setting: "16 A"
– Generator interface (Manual, GenMan, Autostart), default setting: "Autostart"
4. The following parameters must be set when "New Battery" is selected:
– Battery type (VRLA, FLA, NiCd), default setting: "VRLA"
– Nominal voltage of the battery (42 V - 52 V in 2-V steps for FLA and VRLA, 43.2 V to 48 V
in 1.2-V steps for NiCd), default setting: "48.0 V"
– Nominal capacity of the battery (100 Ah - 10000 Ah), default setting: "100 Ah"
☑ After entering all parameters, the following
notification appears.
5. Press <ENTER> to confirm.
☑ The notification shown here is displayed.
6. Press <ENTER> and hold until you hear a beep.
☑ The Sunny Island has started and is in operation.
Displayed text Description
PvOnly Off Grid, no grid, no generator
Gen Stand-alone grid with generator
Grid Power distribution grid
GenGrid Power distribution grid and generator
Adjustable parameters
For more information on adjustable parameters, see section 19”Parameter lists”
(page146).
Note that some parameters can only be changed after entering the installer password (see
section 10.5”Entering the Installer Password” (page76)), or in standby mode (see section
9.2”Stopping the Sunny Island (Standby)” (page63)).