SMA Solar Technology AG Initial Start-up
Technical Description SI5048-TB-TEN110340 61
7. Reconnect the battery current sensor's lines correctly as displayed in the graphic.
Make sure the lines have the correct polarity when doing this.
BatCur+ to terminal 1
BatCur– to terminal 2
8. Start the Sunny Island (see section 9.1”Switching On” (page62)).
9. Check the current direction: "120.06 TotBatCur".
Current direction: Discharging the battery
No generator/grid connected
Consumers are being supplied
The value of the battery current is positive.
Current direction: Charging the battery
Generator/grid connected
Consumers are not/are marginally supplied
Battery is being charged
The value of the battery current is negative.