SMA Technologie AG Parameter Lists
Technical Description SI5048-11:EE4206 Page 131
#222 11 BatTmpCps mV/degC 4.0 battery temperature compensation
absorption time for full charge
4.0 = VRLA
4.0 = FLA
0.0 = NiCd
depending on the setting in QCG
#222 12 AutoEquChrgEna Disable
Enable
Enable activates automatic equalization
charge
#223 Battery Protect Mode
#223 01 BatPro1TmStr h 22 time for starting battery preservation
mode level 1
#223 02 BatPro1TmStp h 6 time for stopping battery preservation
mode level 1
#223 03 BatPro2TmStr h 17 time for starting battery preservation
mode level 2
#223 04 BatPro2TmStp h 9 time for stopping battery preservation
mode level 2
#223 05 BatPro1Soc % 20 SOC limit for preservation mode level
1
#223 06 BatPro2Soc % 15 SOC limit for preservation mode level
2
#223 07 BatPro3Soc % 10 SOC limit for preservation mode level
3
#224 Battery Silent Mode
#224 01 SilentEna Disable
Enable
Disable allows silent mode on the grid
#224 02 SilentTmFlo
(Stby)
h 3 max. time for float charge until
transfer into silent
#224 03 SilentTmMax
(Stby)
h 12 max. time for silent mode until
transfer into float
#225 Battery Current Sensor
#225 01 BatCurSnsTyp
(Stby)
None
60mV
50mV
None current sensor type (60mV, 50mV)
#225 02 BatCurGain60
(Stby)
A/60mV 100 external battery current sensor 60mV
type (visible, if selected with
#225.01 60mV)
#225 03 BatCurGain50
(Stby)
A/50mV 100 external battery current sensor 50mV
type (visible, if selected with
#225.01 50mV)
#225 04 BatCurSnsOfs
(Stby)
A 0 battery current sensor, offset error
(adjustment)
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value