Parameter Lists SMA Technologie AG
Page 132 SI5048-11:EE4206 Technical Description
#230 External Settings
#240 Generator Settings
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description
#230 01 GnGdMod
(Stby)
None
Gen
Grid
GenGrid
None generator and grid operating mode
#230 02 ExtLkTm min 20 lock time after reverse power or relay
protection
#230 03 RtCurCps
External
Internal
Shared
External reactive current compensation
= external (generator)
= internal (Sunny Island 5048)
= shared
#230 04 AcSrcFrqDel Hz 4.8 frequency increase for disconnecting
AC feed-in generators
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description
#241 Start Settings
#241 01 GnAutoEna Off, On On activate generator autostart
#241 02 GnAutoStr 3 number of autostarts
#241 03 GnSocTm1Str % 40 SOC limit for switching on generator
for time 1
#241 04 GnSocTm1Stp % 80 SOC limit for switching off generator
for time 1
#241 05 GnSocTm2Str % 40 SOC limit for switching on generator
for time 2
#241 06 GnSocTm2Stp % 80 SOC limit for switching off generator
for time 2
#241 07 GnTm1Str hhmmss 0 time 1 for generator request (begin
time 1, end time 2)
#241 08 GnTm2Str hhmmss 0 time 2 for generator request (begin
time 2, end time 1)
#241 09 GnPwrEna Off, On Off activate generator request as a result
of power
#241 10 GnPwrStr kW 4 activates generator as a result of
power limit
#241 11 GnPwrStp kW 2 deactivates generator as a result of
power limit
#241 12 GnPwrAvgTm sec 60 average time for power-related
generator start