SMA Technologie AG Parameter Lists
Technical Description SI5048-11:EE4206 Page 133
#242 General Settings
#242 01 GnVtgMin V 172.5 minimum generator voltage
172.5 = 230V_50HZ
172.5 = 220V_60HZ
depending on the setting in QCG
#242 02 GnVtgMax V 250 maximum generator voltage
250 = 230V_50HZ
250 = 220V_60HZ
depending on the setting in QCG
#242 03 GnCurNom A 16 nominal generator current
#242 04 GnFrqNom Hz 50 nominal generator frequency (at
nominal load)
50 = 230V_50HZ
60 = 220V_60HZ
depending on the setting in QCG
#242 05 GnFrqMin Hz 44.64 minimum generator frequency
44.64 = 230V_50HZ
50 = 220V_60HZ
depending on the setting in QCG
#242 06 GnFrqMax Hz 60 maximum generator frequency
60 = 230V_50HZ
70 = 220V_60HZ
depending on the setting in QCG
#242 07 GnStrMod
(Stby)
Manual
Autostart
GenMan
Autostart generator interface
#242 08 GnOpTmMin min 15 minimum generator run time
#242 09 GnStpTmMin min 15 minimum generator stop time
#242 10 GnCoolTm min 5 generator cooling-off time
#242 11 GnErrStpTm h 6 generator stop time for generator
fault
#242 12 GnWarmTm sec 60 warm up time (minimum time required
for generator voltage and frequency
to be within permissible range for
connection)
#242 13 GnRvPwr W 100 permissible generator reverse power
(effective power)
#242 14 GnRvTm sec 30 permissible time for reverse power/
reverse current
#242 15 GnCtlMod Cur
CurFrq
Cur ext. (gen/grid) controller (current
and frequency)
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description