Parameter Lists SMA Technologie AG
Page 134 SI5048-11:EE4206 Technical Description
#250 Grid Settings
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description
#250 01 GdVtgMin V 184 minimum grid voltage
184 = 230V_50HZ
194 = 220V_60HZ
depending on the setting in QCG
#250 02 GdVtgMax V 264.5 maximum grid voltage
264.5 = 230V_50HZ
242 = 220V_60HZ
depending on the setting in QCG
#250 03 GdCurNom A 16 nominal grid current
#250 04 GdFrqNom Hz 50 nominal grid frequency
50 = 230V_50HZ
60 = 220V_60HZ
depending on the setting in QCG
#250 05 GdFrqMin Hz 47.5 minimum grid frequency
47.5 = 230V_50HZ
59.3 = 220V_60HZ
depending on the setting in QCG
#250 06 GdFrqMax Hz 50.2 maximum grid frequency
50.2 = 230V_50HZ
60.5 = 220V_60HZ
depending on the setting in QCG
#250 07 GdVldTm sec 30 minimum time required for grid
(voltage and frequency) to be within
permissible range for connection
30 = 230V_50HZ
300 = 220V_60HZ
depending on the setting in QCG
#250 08 GdMod
GridCharge
GridFeed
GridCharge
Grid interface:
= charging only (only current from
the grid)
= feedback also possible
#250 09 GdRvPwr W 100 permissible grid reverse power
(effective power)
#250 10 GdRvTm sec 5 permissible time for grid reverse
power