SMA Technologie AG Parameter Lists
Technical Description SI5048-11:EE4206 Page 135
#260 Relay Settings
Menu
no.
Para-
meter
no.
Parameter name Range/
Short
descr.
Default
value
Description
#261 Relay General
#261 01 Rly1Op
Off
On
AutoGn
AutoLodExt
AutoLodSoc
Tmr1
Tmr2
AptPhs
GnRn
ExtVfOk
GdOn
Error
Run
Ens1
Ens2
BatFan
AcdCir
AutoGn Function of relay 1:
= switched off
= switched on
= automatic generator connection
= automatic disconnection of
external loads
= automatic disconnection of loads
due to SOC
= programmable timer 1
= programmable timer 1
= absorption phase is active
= generator is running
= ext. voltage and frequency in
permissible range
= ext. grid is connected
= error
= operation
(= currently has no function)
(= currently has no function)
= battery room fan
= electrolyte pump
#261 02 Rly2Op see
#261.01
AutoLodSoc
Function of relay 2:
for details, see #261.01
#262 Relay Load
#262 01 LodSocTm1Str % 30 SOC limit for load shedding start for
t1
#262 02 LodSocTm1Stp % 50 SOC limit for load shedding stop for
t1
#262 03 LodSocTm2Str % 30 SOC limit for load shedding start for
t2
#262 04 LodSocTm2Stp % 50 SOC limit for load shedding stop for
t2
#262 05 LodTm1Str hhmmss 0 load shedding time 1
(begin time 1, end time 2)
#262 06 LodTm2Str hhmmss 0 load shedding time 2
(begin time 2, end time 1)
#263 Relay Timer
#263 01 RlyTmr1StrDt yyyymmdd 20060101 start date timer 1
#263 02 RlyTmr1StrTm hhmmss 0 start time for relay control
timer 1
#263 03 RlyTmr1Dur hhmmss 0 run time for relay control timer 1
#263 04 RlyTmr1Cyc Single
Daily
Weekly
Single repeated cycle time for timer 1