11 Troubleshooting
SMA Solar Technology AG
Operating manual STPxx-US-50-BE-en-11 81
Explanation:
The inverter has switched off due to excessive temperature.
Corrective measures:
Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft
brush.
Ensure that the inverter has sufficient ventilation.
Ensure that the inverter is not exposed to direct solar irradiation.
Ensure the maximum ambient temperature is not exceeded.
11.1.25 Event 6511
Event message:
Overtemperature
Explanation:
An overtemperature has been detected in the choke area.
Corrective measures:
Clean the cooling fins on the rear of the enclosure and the air ducts on the top using a soft
brush.
Ensure that the inverter has sufficient ventilation.
Ensure that the inverter is not exposed to direct solar irradiation.
11.1.26 Event 6512
Event message:
Minimum operating temperature not reached
Explanation:
The inverter will only recommence grid feed-in once the temperature has reached at least −25°C.
11.1.27 Event 6602
Event message:
Overvoltage grid (AF)
Explanation:
The effective value of the grid voltage is above the permitted voltage threshold values for a
specified period of time (AF limit).