HMC6 Power Management Controller User Manual Page 74 of 87
current and other genset priority.
If enabled this function, transfer any controller
mode (button or input port) will change all genset
controller modes on the busbar.
Safety Level Alarm
Action
If enabled this function, in semi-auto mode, the
safety trip and safety trip and stop alarm will
perform the corresponding alarm action.
If disabled this function, in semi-auto mode, the
safety trip and safety trip and stop alarm will only
alarm but not act.
If start mode set as “Duty Running Hours”, firstly,
prior to start the unit with the least running time.
When running the set to the pre-set duty value, the
next unit with less running time starts up.
0: Gen Power (%)
1: Available Power
Loading percentage of busbar that scheduled to
start other units.
Loading percentage of busbar that scheduled to
stop other units.
Power left of busbar that scheduled to start other
units.
Power left of busbar that scheduled to stop other
units.
Max. Network
Connected Genset
Number
The max. adjusting gensets of network
connected on the current busbar;
Failed to Unload and
Open
(0-1)
(0-100.0) %
(0-3600)s
If enabled this function, it will judge unload failure
after genset unload delay 180s; and it will open
when load is less than 10.0%, otherwise it will not
open.
If disabled this function, it will judge unload
failure after genset unload delay 180s; and it is
only alarm but not open.
Active Power
Adjusting Limit
The max. adjusting deviation of current power
apart from target power value;
Inactive Power
Adjusting Limit
The proportion of load frequency adjustment PID
coefficient in the whole load active power
adjustment coefficient.
The proportion of load voltage adjustment PID