HMC6 Power Management Controller User Manual Page 50 of 87
No.
Items
Parameter Range
Default
Description
12
Operate Stop Delay
(0-3600)s
1
Stop delay caused by human triggered
(e.g. manual transfer priority, high
consumer request and etc.)
13
Cooling Delay
(0-3600)s
0
High speed cooling time before stop
output.
14
HC Stable Delay
(0-1000)s
5
After busbar retardant power meet with
high consumer request, high consumer
ACK output after this delay.
15
HC ACK Delay
(0-1000)s
5
After busbar retardant power meet with
high consumer request, high consumer
ACK output after “HC Stable Delay”.
11.3 GENERATOR SETTING
Table 21 Generator Parameter Settings
No.
Items
Parameter Range
Default
Description
Generator
1
AC System
(0-3)
0: 3P4W
0: 3 phase, 4 wire (3P4W);
1: 3 phase, 3 wire (3P3W);
2: 2 phase, 3 wire (2P3W);
3: 1 phase, 2 wire (1P2W).
2
Rated Voltage
(30-30000)V
230
To offer standards for detecting of
generator’s over/under voltage. (It is
primary voltage when using voltage
transformer; it is line voltage when AC
system is 3P3W while it is phase
voltage when using other AC system).
3
Loading Voltage
(0-200)%
95
Setting value is percentage of
generator rated voltage. Detect when
controller prepare loading. When
generator voltage under load voltage,
won’t enter into normally running.
4
Crank Success Volt
(0-200)%
30
To offer standards for detecting crank
disconnect voltage is satisfied or not.
5
Rated Frequency
(10.0-75.0)Hz
50.0
To offer standards for detecting of
over/under/load frequency.
6
Loading Frequency
(0-200)%
85
Setting value is percentage of
generator rated frequency. Detect
when controller prepare loading. When
generator frequency under load
frequency, it won’t enter into normal
running.
7
Crank Success Frequency
(0-200)%
65
To offer standards for detecting crank