How to save changes to memory
If you make any changes to a Labels or Password
then you must save these to the NVM (Non Volatile
Memory) or Memory of the panel.
"
Changes made to labels and
password can be saved to the panel
memory (NVM), this can only be done
when there are no disablements present
on the system.
The following procedures assume a customer
password (PIN) is setup at the panel.
a. Press the MENU ON/OFF button.
b. Press the F2 button to select [Set Up].
c. Press the F4 button to select [UserCode].
Notice a message on the display 'Enter access
code' followed by a flashing cursor. Use the
keypad to input your PIN code and then press
the Enter button.
d. Press the F4 button to select <etc> and then
press the F3 button to select [Save].
"
The 'Save' option is only
available if Access level 2 PIN is set up.
e. Press the F2 button to select [Enter]. Observe
confirmation of data backed up.
How to view active events
An active event is an event that is still present and has
not cleared. You can view all active Fire, Fault or
Disablement events.
a. Press MENU ON/OFF.
b. Press the F3 button to select [Info].
"
Ignore step c. if an external
printer is not fitted or is switched off.
c. To display the event(s): Press the F1 button to
select [Display]. Notice 'Display' appears on the
display.
To print the event(s): Press the F2 button to
select [Print]. Notice 'Print' appears on the
display.
d. Press the F1 button to select [Active]. Notice
'Active' appears on the display.
If you want to view events on the local panel
card by card basis then press the F3 button to
select [Card] notice 'on card' appears on the
display, then enter the card number.
If you want to view events at another node in a
networked system, then you will need to know
the node number. Press the F4 button to select
[Node] and enter a node number from a range
1 to 255.
e. Press the F2 button to select [Enter]. Notice all
of the active Fire, Fault and Disablement events
are displayed in turn. Press the F2 [Previous]
and F3 [Next] button to scroll through the
displayed events.
f. Press the F4 button to select [Quit], when
viewing of events is complete.
21