How to enable/disable a zone
A zone is a subdivision of your premises protected by
the fire alarm system. There can be up to 128 zones
configured in a system. Any zone operation can be
disabled or enabled. You will need the zone number,
this you can find in the site specific documentation
held by the person responsible for the fire alarm
system.
a. Press the MENU ON/OFF key.
b. Press the F1 button to select [Control].
c. Press the F4 button to select [UserCode].
Notice a flashing cursor and a message on the
display 'Enter access code'. Use the keypad to
input your PIN code and then press the Enter
button.
d. To disable a zone: Press the F2 button to select
[Disable]. This puts 'Disable' on the display.
To enable a zone: Press the F1 button to select
[Enable]. This puts 'Enable' on the display.
e. Press the F4 button to select <etc> and then
press the F2 button to select [Zone]. Notice
'Zone' appears on the display followed by a
flashing cursor. Use the keypad to input a zone
number or range (1-128).
f. Press the F2 button to select [Enter]. Notice the
action has been processed and a message
appears on the display 'Zone n enabled' or
'Zone n disabled'. The Disablement light will be
illuminated upon disablement of any zone.
How to enable/disable Sensing
"
It is only possible to disable a
Manual Call Point (MCP) individually, not
as part of a range. Disabling a MCP is
however, not recommended.
A sensing device such as sensor or MCP connected
to the loop circuit of the system can be
disabled/enabled. You will need the device number
and loop number, this you can find in the site specific
documentation, held by the person responsible for the
fire alarm system.
a. Press the MENU ON/OFF key.
b. Press the F1 button to select [Control].
c. Press the F4 button to select [UserCode].
Notice a flashing cursor and a message on the
display 'Enter access code'. Use the keypad to
input your PIN code and then press the Enter
button.
d. To disable a device: Press the F2 button to
select [Disable]. This puts 'Disable' on the
display.
To enable a device: Press the F1 button to
select [Enable]. This puts 'Enable' on the
display.
e. Press the F1 button to select [Sensing]. Notice
'Device' followed by a flashing cursor appears
on the display. Use the keypad to input an
device number or range (1-200).
f. Press the F2 button to select [Loop]. Notice
'Loop' followed by a flashing cursor on the
display. Use the keypad to input a loop number
or range (1-2).
g. Press the F2 button to select [Enter]. Notice the
action has been processed and confirmed by a
message either: 'Device(s) enabled' or
'Device(s) disabled'. Notice that the
Disablement light is illuminated upon
disablement of any system device.