10
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
free areafree area
UNPACKING AND INSTALLATION
OF THE UNIT
3
3.3 ENVIRONMENTAL REQUIREMENTS.
The recommended operating temperature, humidity and altitude values are listed in the technical speci cations
table. Cooling systems may be required to maintain these values.
Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or
chemical solutions).
The UPS is not designed for outdoor use.
Do not expose the UPS to direct sunlight or to sources of excessive heat.
A space of at least 40 cm must be left at the back for adequate ventilation (see  gure 3.3-1).
The UPS switches are accessed from the front; a space of at least 1.5 metres should be left at the front of the UPS
for maintenance purposes.
Adequate access must be ensured on both sides (see  gure 3.3-2).
Do not put any object on the upper part of the UPS.
3.3-1
3.3-2
MASTERYS
IP+
BATTER
CABINET
BATTERY
CABINET
40 cm
1,5 m
MASTERYS
IP+
40 cm1,5 m
20 cm20 cm20 cm
3.3-3
Place the UPS in the installation area, then secure it to the  oor.
40 cm
door
door