UNPACKING AND INSTALLATION
OF THE UNIT
3
3.3 ENVIRONMENTAL REQUIREMENTS.
• The recommended operating temperature, humidity and altitude values are listed in the technical speci cations
table. Cooling systems may be required to maintain these values.
• Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or
chemical solutions).
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or to sources of excessive heat.
• A space of at least 40 cm must be left at the back for adequate ventilation (see gure 3.3-1).
• The UPS switches are accessed from the front; a space of at least 1.5 metres should be left at the front of the UPS
for maintenance purposes.
• Adequate access must be ensured on both sides (see gure 3.3-2).
• Do not put any object on the upper part of the UPS.
3.3-1
3.3-2
MASTERYS
IP+
BATTER
CABINET
BATTERY
CABINET
40 cm
1,5 m
MASTERYS
IP+
40 cm1,5 m
20 cm20 cm20 cm
3.3-3
Place the UPS in the installation area, then secure it to the oor.
40 cm
door
door