8.1 “ALLARMS” MENU
This is used to display all the alarms that are active at the time of access.
The alarms menu is activated automatically when an alarm condition occurs.
ALARMS menu
Code Mimic panel description Meaning
A00 GENERAL ALARM
A01 BATTERY ALARM Battery circuit failure or faulty operation.
A02 OUTPUT OVERLOAD Power required in output over the limits.
A06 AUXILIARY MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the bypass have been
exceeded.
A07 OVER TEMPERATURE Temperature excessive or ventilation problems.
A08 MAINTENANCE BYPASS ACTIVE Q5 in position 1.
A17 IMPROPER CONDITION OF USE Improper conditions of use veri ed (load, mains, and temperature).
A18 BLOCKING INVERTER FOR OVERLOAD Inverter shutdown due to overload.
A20 WRONG CONFIGURATION Error in the con guration parameters (e.g. di erent parameters
between several UPSs in parallel).
A22 INPUT MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the recti er have been
exceeded.
A23 RECTIFIER GENERAL ALARM Recti er fault.
A25 INVERTER GENERAL ALARM Inverter fault.
A26 BATTERY CHARGER GENERAL ALARM Battery charger fault.
A29 BYPASS GENERAL ALARM Bypass fault.
A30 STOP FOR OVERLOAD The duration of the overload has inhibited the bypass.
A32 MODULE 1 GENERAL ALARM Module 1 failure.
A33 MODULE 2 GENERAL ALARM Module 2 failure.
A38 EXTERNAL ALARM 1 Signalling from ADC input.
A39 EXTERNAL ALARM 2 Signalling from ADC input.
A40 EXTERNAL ALARM 3 Signalling from ADC input.
A41 EXTERNAL ALARM 4 Signalling from ADC input.
A42 E-SERVICE GENERAL ALARM Alarm that generates automatic sending of a signal to the support
centre (if the service has been activated).
A43 REDUNDANCY LOST The power required by the load no longer allows the preset
redundancy N+x to be maintained (for UPSs in parallel only).
A44 PERIODIC SERVICE CHECK-UP Warning for periodic check by support service.
A47 MAX BATTERY TEMPERATURE Control of the temperature of battery cabinet.
A49 BATTERY DISCHARGED The energy available in the battery has been used up.
A51 OPTION BOARD GENERAL ALARM Fault related to the optional PCBs in the slots.
A56 GENERATOR SET GENERAL ALARM Minor alarm on generator set.
A57 GENERATOR SET FAULT Major alarm on generator set.
A58 E.S.D. ACTIVATED The remote emergency shutdown command has been activated.
A59 BATTERY CIRCUIT OPEN The battery switch is open.
A60 FAN FAILURE Fans faulty or blocked.
A61 PHASE ROTATION FAULT Wrong phase cycle direction.