ITALIANOENGLISH
48
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
10
PROBLEM SOLVING
A61: wrong phase cycle direction.
The phase cycle sequence is incorrect. In this case, invert two phases of the input mains. For a UPS with separate
auxiliary mains, exchange the two phases of the auxiliary mains only.
10.2 UPS ALARMS.
A01: battery alarm.
Failure or problem on the battery circuit. Check that the battery switch is closed.
A18: inverter blocked due to overload.
Reduce the load rate applied to the UPS and reset the alarms.
A20: wrong con guration.
Error in the con guration parameters; please contact the support service.
A30: block due to overload.
Reduce the load rate applied to the UPS and reset the alarms.
A42: T.Service general alarm.
The MASTERYS™ products can be remotely serviced. This alarm indicates that a procedure for analysing the UPS
failure has been activated by the support centre (if an e-service contract has been concluded).
A44: programmed control.
The equipment has to undergo periodic checks by the support service in order to ensure optimum perform-
ance and e ciency. If the “Programmed Control” signal appears on the mimic panel, the equipment should be
inspected by an adequately trained technician.
A59: battery circuit open.
Battery switch open.
A60: fan failure.
Fault in the ventilation system; check that the air inlet at the front and the air outlet at the back of the UPS are not
obstructed.