UNPACKING AND INSTALLATION
OF THE UNIT
3
3.5 ELECTRICAL REQUIREMENTS.
The installation and the system must comply with national plant regulations.
The electrical distribution panel must have a protection and sectioning system installed for the input mains and the
auxiliary mains. If a di erential switch is installed on the mains power switch (optional), it must be inserted upstream
from the distribution panel.
The table below show the size of the input protection devices recommended for correct installation.
WARNING!
The default transformer is normally connected to the output.
Size of the input protection devices
UPS
[kVA]
Magneto-thermal
input
1
[A]
Magneto-thermal
Auxiliary Mains
1
[A]
Di erential
input
5
[A]
Input cable
core size
[mm
2
]
Output/Aux
cable core size
[mm
2
]
Battery cable
core size
[mm
2
]
Battery
protection
4
[A]
single parallel
2
single parallel
2
selective type
5
min-max
3
min-max
3
10 3/1
32 40
100 125 0.5 6÷35 16÷50 6÷35 50 Gr
100
if common
input mains
125
if common
input mains
15 3/1
32 40
100 125 0.5 6÷35 25÷50 6÷35 50 Gr
100
if common
input mains
125
if common
input mains
20 3/1
40 63
125 160 0.5 10÷35 35÷50 10÷35 50 Gr
125
if common
input mains
160
if common
input mains
30 3/1
63 80
160 200 0.5 16÷35 50 16÷35 100 Gr
160
if common
input mains
200
if common
input mains
10 3/3 32 40 32 40 0.5 6÷35 6÷35 6÷35 50 Gr
15 3/3 32 40 32 40 0.5 6÷35 6÷35 6÷35 50 Gr
20 3/3 40 63 40 63 0.5 10÷35 10÷35 10÷35 50 Gr
30 3/3 63 80 63 80 0.5 16÷35 16÷35 16÷35 100 Gr
40 3/3 80 100 80 100 0.5 25÷35 25÷35 25÷35 100 Gr
1
Recommended magneto thermal switch: four poles with intervention threshold ≥ 10 In
2
In systems with two or more UPSs operating in a redundant or power parallel con guration.
3
Determined by the size of the terminals.
4
Protection on the external battery cabinet.
5
Caution! Use type B four-pole selective (S) circuit breakers. Load leakage currents are added to those generated by the UPS and during transitory
phases (power failure and power return) short current peaks may occur. If loads with high leakage current are present, adjust the di erential
protection. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the
de nitive load, so as to prevent the sudden activation of the above switches.