EasyManuals Logo

socomec MASTERYS IP Plus User Manual

socomec MASTERYS IP Plus
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
ITALIANOENGLISH
56
IOMMASIPXX09-GB 04
10-40 kVA
MASTERYS IP+
MASTERYS IP+ allows both parallel power and parallel 1+1 redundant con gurations.
WARNING!
Parallel power con guration is possible ONLY with the transformer connected in the input (Mains
or Auxiliary Mains).
WARNING!
Parallel with transformer connected to the output is possible only by using the speci c kit
including two speci c UPS (one with transformer and one without transformer) for 1+1 redundant
con guration.
WARNING!
Parallel con guration must only be activated by SOCOMEC UPS quali ed personnel.
Use the UPS in accordance with the technical speci cations given in this Installation and Operating Manual.
The UPS units connected in parallel con guration are identical to a standard UPS, as a result safety, shipping and
installation recommendations in chapters 2 and 3 also apply.
INSTALLATION.
Parallel power con guration:
Please check that the transformer is connected on the input side (Mains or Aux Mains - refer to paragraph 3.5).
UPS units operating in parallel are interconnected using control cables and are con gured di erently depending
on the position they are assigned. For this reason the units have a position label:
The “LEFT label means that the unit must be positioned to the left.
The “RIGHT label means that the unit must be positioned to the right.
The “INTERNAL label (used only on systems with three UPS) means that this unit must be positioned between
the two other cabinets.
Parallel 1+1 redundant con guration:
UPS units operating in parallel 1+1 redundant con guration are interconnected using control cables and are
con gured di erently depending on the position they are assigned. For this reason the units have a position
label:
The “LEFT label means that the unit must be positioned to the left (UPS with transformer con gured as concentrator).
The “RIGHT label means that the unit must be positioned to the right (UPS without transformer).
The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough
room for an external battery cabinet to be inserted beside each UPS.
WARNING!
The UPS must be secured to the  oor (see paragraph 3.3).
POWER CONNECTIONS.
The power supply to each unit must be protected as indicated in the table in paragraph 3.4.
The cross section and length of the input and output cables must be identical for all the units.
The phase rotation must be the same for all units connected in parallel.
PARALLEL CONFIGURATION

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec MASTERYS IP Plus and is the answer not in the manual?

socomec MASTERYS IP Plus Specifications

General IconGeneral
Brandsocomec
ModelMASTERYS IP Plus
CategoryUPS
LanguageEnglish

Related product manuals