Appendix B: Technical Specifications
SolarEdge Installation Guide MAN-01-00057-2.2
61
SE5K
SE7K
SE8K
SE9K
SE10K
SE12.5K
SE15K
SE16K
SE17K
Unit
Input
Maximum DC power
1
(Module STC)
5500
7700
8800
9900
11000
13700
16500
17600
18700
W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
950
Vdc
Nominal DC input
voltage
750
Vdc
Maximum input
current
8.5
12
13.5
15
16.5
21
22
23
23
Adc
Maximum back-feed
current
0
Adc
Reverse-polarity
protection
Yes
Ground-fault isolation
detection
1MΩ Sensitivity
Overvoltage category
III
Maximum inverter
efficiency
98
%
European weighted
efficiency
97.3
97.3
97.5
97.5
97.6
97.7
97.6
97.7
97.7
%
Night-time power
consumption
< 2.5
W
Additional Features
Supported
communication
interfaces
RS485, RS232, Ethernet, ZigBee (optional)
Standards Compliance
Safety
IEC-62103 (EN50178), IEC-62109
Grid connection
standards
VDE-AR-N-4105, VDE 0126-1-1, AS-4777, RD-1663, DK 5940
Emissions
IEC61000-6-2, IEC61000-6-3, IEC61000-3-11, IEC61000-3-12, FCC part15 class B
WEEE, RoHS
Yes
Installation Specifications
AC output
Cable Gland - diameter 15-21
mm
DC input
2 MC4 pairs
Maximum installation
height
2000
m
Dimensions (WxLxH)
540 x 315 x 260
mm
Weight
33.2
kg
1
For detailed information regarding allowed oversizing, refer to
http://www.solaredge.com/files/pdfs/inverter_dc_oversizing_guide.pdf