Appendix B: Technical Specifications
SolarEdge Installation Guide MAN-01-00057-2.2
62
SE5K
SE7K
SE8K
SE9K
SE10K
SE12.5K
SE15K
SE16K
SE17K
Unit
Operating
temperature range
1
-20 - +60 (M40 version -40 to + 60)
°C
Operating humidity
non condensing
<95
%
Cooling
Fan (user replaceable)
Noise
< 50
dBA
Protection rating/
Environmental
category
IP65 Outdoor and indoor
Maximum altitude
2000
m
Pollution degree
classification
(inside/outside)
2/3
Bracket mounted (bracket provided)
Recommended circuit breaker/fuse size to use at the connection point of the SolarEdge inverter to
the grid:
Inverter
Maximum Output Current (A)
Suggested Fuse Rating (A)
SE2200
12
16
SE3000
16.5
20
SE3500
19.5
25
SE4000
22
25
SE4000-16A
16
20
SE5000
27
32
SE6000
27
32
SE5k
8
10
SE7k
11.5
16
SE8k
13
16
SE9k
14.5
20
SE10k
16
20
SE12.5k
20
25
SE15k
23
25
SE16k
25.5
32
SE17k
26
32
1
For inverter power de-rating refer to the application note at the following link: http://www.solaredge.com/files/pdfs/se-
temperature-derating-note.pdf