Setting the country and reactive power characteristic curve
Note
The country can only be set once!
1. Press  to select a country.
2. Press SET briefly. The country is adopted.
3. Press SET for a longer time.
If a reactive power characteristic curve is not prescribed
for the selected country then finish initial commission-
ing (see below).
4. Press  to select the reactive power characteristic
curve according to the local regulations.
5. Press SET briefly. The characteristic curve is adopted.
6. Press SET for a longer time. If Default char. curve
or Char. curve cos φ = 1 was selected in step 4 then
proceed with step 18.
7. Press SET briefly. The setting value flashes.
8. Press  to change the number of nodes.
9. Press SET briefly. The value is adopted.
10. Press SET for a longer time.
11. Press  to select a setting value for the first node. P %
has predefined fixed values for the first and last node
(000 %, 100 %).
12. Press SET briefly. The setting value flashes.
13. Press  to change the value.
14. Press SET briefly. The change is adopted.
15. Repeat steps 11 to 14 for the other setting value.
16. Press SET for a longer time.
17. Repeat steps 11 to 16 for the setting values of the re-
maining nodes.
18. The characteristic curve is displayed graphically (example
in fig. at left).
19. Press SET for a longer time.
Finishing initial commissioning
1. Press ESC to jump stepwise backwards and correct set-
tings or
press and hold SET for a longer period of time to finish
initial commissioning.