45 © STULZ GmbH – all rights reserved EN/09.2017/G44
cybercool indoor chiller original instructions
Start the chiller by pressing the Start/Stop-key on the C7000AT
controller or by typing the command “state start” on the notebook.
Check after 20 minutes operation, whether bubbles are visible in
the sight glass of the liquid line. If this is the case, refrigerant might
have escaped by a leak.
Check the circuit on leaks, eliminate these and top up the circuit
with refrigerant in regard of the chapter „Maintenance“.
Check the oil level at the compressor in respect of the right level.
The oil level must be between the lower quarter and the middle of
the sight glass.
Check the current consumption of the compressors and the pump
comparing it with the values of the e-data sheet.
NOTICE
Risk of Oil dilution. Bearing malfunction.
It is important to ensure that new compressors are not subjected to liquid abuse. If the compres-
sor is equipped with a crankcase heater, turn it on 12 hours before starting the compressor.
Sight glass
Service port X15 in the e-box.
Oil sight glasses