Page | 45
GS10000
RS485 3
BPE
CAN 0
ABOET
CAN 0
VISION
Group
CAN 13
Alpha
CAN 0
Backbone
B-LFP51.2V
100Ah and B-
LFP51.2V
125Ah
CAN 0
Float voltage 54.5V
Absorption V 55.00V
Disable equalisation
0 Days
Shutdown 20%
Low Batt 35%
Restart 50%
When communications between battery and inverter does not exist, do not
overcharge your battery bank (current or voltage). Many lithium batteries are limited
to 100A, some are lower and some are higher. Ensure that voltage and current
specifications provided by the battery manufacturer are followed.
If you are using lead acid batteries then follow the equation of C x 0.25 which means
that the maximum charge or discharge you can apply to a battery is a quarter of the
AH rating of the overall battery array. Eg.; A 200Ah battery array composed of 4 x
200Ah batteries in series has a maximum discharge of only 50Ah (200 x 0.25 = 50)
Also, ensure the cable is thick enough to support the current and the fuses
connected are of the correct rating as per the recommendations of battery
manufacturers.