no export is performed. The unit allows small amounts of power to flow from the Grid
(100W Zero Export Power) to prevent any back-flow. In this example, the solar PV is
prioritised to supply the Load first and then subsequently, charge the battery.
5.15. Grid Supply Voltage and Frequency – Grid Supply Page
On the Settings Menu, click on the GRID icon.
Set the Minimum Grid Input Voltage (‘Grid Vol Low’)
Set the Maximum Grid Frequency (‘Grid Hz High’)
Set the Minimum Grid Frequency (‘Grid Hz Low)
Select the correct Grid Type in your local area, otherwise the machine will not work
or be damaged.
Select the correct Grid Frequency in your local area.
Active Power and Reactive Power Setting (Go to GRID-SET2): The inverter is capable
of producing reactive power and feeding it into the Grid through this setting. Feed-In
management can be controlled directly by the Grid company through a dedicated
communication port.
What this page displays:
Grid frequency setting
Grid type (normally 230V three-
phase)
What you can do from this page:
Change grid’s frequency setting
(normally 50 Hz)
Set the Maximum Grid Input
Voltage (‘Grid Vol High’)