SUNSYNK MAX | Installer Manual50
NOTE:
When communications between the battery and inverter do not exist, do not overcharge your
battery bank (current or voltage). Many lithium batteries are limited to 100A, some are lower, and
some are higher. Ensure that voltage and current specications provided by the battery
manufacturer are followed.
If you are using lead acid batteries, then follow the equation of C x 0.25, which means that the
maximum charge or discharge you can apply to a battery is a quarter of the AH rating of the overall
battery array. E.g.: A 200Ah battery array composed of 4 x 200Ah batteries in series has a maximum
discharge of only 50Ah (200 x 0.25 = 50)
Also, ensure the cable is thick enough to support the current and that the connected fuses are of the
correct rating per the battery manufacturers' recommendations.
Brand Model
48V
Storage
Inverter
RS485
or CAN
Inverter
Setup
Notes
Blue Nova HC
BN52V-280-14.5K HC
CAN 0
Can be used with or with-
out BMAC
BN52V-560-29K HC CAN 0
https://www.bluenova.
co.za/wp-content/up-
loads/2015/11/BN-User-
Manual-HC_v102.pdf
BN52V-840-43.6K HC CAN 0
BN52V-1120-58.2K HC CAN 0 CANH = Pin 7
BN52V-1400-72.8K HC CAN 0 CANL = Pin 8
Blue Nova
Rack Series
BN52V-840-43.6K BR
CAN 0
BlueNova-BMAC-Manu-
al-v4.pdf
BN52V-1120-58.2K BR CAN 0