SUNSYNK MAX | Installer Manual15
Battery Connection
For safe operation and compliance, a separate DC over-current protector or disconnect device is required
between the battery and the inverter. In some applications, switching devices may not be required but
over-current protectors are still required. Refer to the typical amperage in the table below for the required
fuse or circuit breaker size.
Model Wire Size Cable (mm
2
) Torque Value (max.)
16kW 1/0 AWG 53 12.5N.m
12 mm
82~90mm
[(3.23 in.)to(3.54 in.)]
(0.47 in.)
WARNING
All wiring/connecting must be performed by qualied personnel. Before making the nal DC con-
nection or closing the DC Breaker/disconnection device, ensure the inverter unit is wired correctly. A
reverse-polarity connection on the battery will damage the inverter.