Appendix C: NFPA Standard-Specific Requirements
FM-Approved Releasing Devices
36 The PDRP-1001 PN 50734:C 03/11/99
Appendix C: NFPA Standard-Specific Requirements
The PDRP-1001/PDRP-1001A/PDRP-1001E has been designed for use in commercial,
industrial, and institutional applications and meets the requirements for service under
the National Fire Protection Association (NFPA) Standards outlined in this appendix.
The minimum system components required for compliance with the appropriate NFPA
standards are listed below.
PDRP-1001/PDRP-1001A/PDRP-1001E Control Panel
containing the main control
board, cabinet (backbox and door), main supply transformer and power supply.
Batteries
(refer to Appendix A for Standby Power Requirements).
Initiating Devices
- connected to one of the control panel’s Initiating Device Circuits.
Notification Appliances
- connected to one of the control panel’s Notification
Appliance Circuits.
Releasing Devices
- connected on one of the control panel’s Releasing Circuits.
The following additional equipment is needed for compliance with the NFPA standards
listed below.
NFPA 72 Signaling Systems for Central Station Service (Protected Premises Unit)
NOTI•FIRE 911AC DACT* - for connection to a compatible listed Central Station
DACR or Protected Premises Receiving Unit. This unit must be installed as outlined in
Figure 13.
NFPA 72 Auxiliary Fire Alarm System
4XTM Transmitter Module for connection to a compatible listed Local Energy
Municipal Box. This unit must be installed as outlined in Figure 15.
NFPA 72 Remote Station Fire Alarm System
4XTM Transmitter Module for connection to Fire•Lite RS82-9 Remote Station
Receiver. See Figure 16 for installation instructions.
OR
NOTI•FIRE 911AC DACT* - For connection to a compatible listed remote station
DACR. This unit must be installed as outlined in Figure 13 and Figure 14.
*Applications which require the NOTI•FIRE 911AC are not FM approved
.