1 The PDRP-1001/PDRP-1001A/PDRP-1001E
Input Circuits
6 The PDRP-1001 PN 50734:C 03/11/99
1 The PDRP-1001/PDRP-1001A/PDRP-1001E
Features
Microprocessor-controlled
Alarm and trouble resound
Four Class B (Style B)/Class A (Style D) Initiating Device Circuits
Two Class B (Style Y)/Class A (Style Z) Notification Appliance Circuits
Two Class B (Style Y) Release Circuits
General alarm and trouble relays
Optional module for 4 zone/function relays (4XZM)
Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm Systems
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator RZA-4X). Requires LED Interface
Module (4XLM)
Optional digital communicator (NOTI•FIRE 911AC)*
Complies with NFPA 72 Central Station and NFPA 72 Remote Station Fire Alarm
Systems
Designed for sprinkler standards NFPA 13, 15, and 16
Disable/enable controls per initiating zone
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release Circuits
RMS regulated output power, 2.25 amps
7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
Resettable and non-resettable regulated power outputs
Extensive transient protection
Watchdog timer to supervise microprocessor (includes MICRO FAIL LED)
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5" wide by 16" high by 5" deep
Dead-front dress panel option (DP-4X)
Trim ring for flush mount between 16" center studs (TR-4XR)
Cross-zone (double-interlock) option
Municipal Box output
Interface Module (4XLM)
Dual hazard operation
Adjustable discharge timer
*
Applications which require the NOTI•FIRE 911AC are not FM approved
.
Circuits
Input Circuits
Manual Release/Detector Circuit 1, Class A (Style D)/Class B (Style B)
Detector Circuit 2, Class A (Style D)/Class B (Style B)
Waterflow, Class A (Style D)/Class B (Style B)
Supervisory, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Alarm/Waterflow Bell, Class A(Style Z)/Class B (Style Y)
Waterflow/Supervisory Bell, Class A(Style Z)/Class B (Style Y)
Releasing Circuit 1, Class B (Style Y)
Supervisory Bell/Release Circuit 2, Class B (Style Y)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the System Sensor PDRP-1001 and is the answer not in the manual?

System Sensor PDRP-1001 Specifications

General IconGeneral
BrandSystem Sensor
ModelPDRP-1001
CategoryControl Panel
LanguageEnglish

Related product manuals