1 The PDRP-1001/PDRP-1001A/PDRP-1001E
Input Circuits
6 The PDRP-1001 PN 50734:C 03/11/99
1 The PDRP-1001/PDRP-1001A/PDRP-1001E
Features
• Microprocessor-controlled
• Alarm and trouble resound
• Four Class B (Style B)/Class A (Style D) Initiating Device Circuits
• Two Class B (Style Y)/Class A (Style Z) Notification Appliance Circuits
• Two Class B (Style Y) Release Circuits
• General alarm and trouble relays
• Optional module for 4 zone/function relays (4XZM)
• Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm Systems
• Optional volt/amp meter module (4XMM)
• Optional supervised remote annunciator RZA-4X). Requires LED Interface
Module (4XLM)
• Optional digital communicator (NOTI•FIRE 911AC)*
• Complies with NFPA 72 Central Station and NFPA 72 Remote Station Fire Alarm
Systems
• Designed for sprinkler standards NFPA 13, 15, and 16
• Disable/enable controls per initiating zone
• Last Event Recall
• Battery/Earth fault supervision
• Fuse protection on all Notification/Release Circuits
• RMS regulated output power, 2.25 amps
• 7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
• Resettable and non-resettable regulated power outputs
• Extensive transient protection
• Watchdog timer to supervise microprocessor (includes MICRO FAIL LED)
• Output circuits protected against false activations
• Slide-in zone identification labels
• Steel cabinet 14.5" wide by 16" high by 5" deep
• Dead-front dress panel option (DP-4X)
• Trim ring for flush mount between 16" center studs (TR-4XR)
• Cross-zone (double-interlock) option
• Municipal Box output
• Interface Module (4XLM)
• Dual hazard operation
• Adjustable discharge timer
*
Applications which require the NOTI•FIRE 911AC are not FM approved
.
Circuits
Input Circuits
Manual Release/Detector Circuit 1, Class A (Style D)/Class B (Style B)
Detector Circuit 2, Class A (Style D)/Class B (Style B)
Waterflow, Class A (Style D)/Class B (Style B)
Supervisory, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Alarm/Waterflow Bell, Class A(Style Z)/Class B (Style Y)
Waterflow/Supervisory Bell, Class A(Style Z)/Class B (Style Y)
Releasing Circuit 1, Class B (Style Y)
Supervisory Bell/Release Circuit 2, Class B (Style Y)