4-38
Group 10 PID Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
10-49
Differential Time (D) of Fire Mode
0.00~10.00 0.00 s O O O
Group 11 Auxiliary Parameters
Code Parameters Setting Range DefaultUnit
Control Mode
Attribute
V/F SLV
PM
SLV
11-00 Direction Lock Selection
0:Allow Forward and Reverse Rotation
1:Only Allow Forward Rotation
2:Only Allow Reverse Rotation
0 - O O O
11-01 Carrier frequency
0:Carrier Output Frequency Tuning
1~16:1~16KHz
* - O O O *1
11-02
Soft PWM Function
Selection
0:Disable
1:Soft PWM
0 - O O O
11-03
Automatic carrier
lowering selection
0:Disable
1:Enable
0 - O X X
11-04
S-curve Time Setting at
the Start of Acceleration
0.00~2.50 0.20 s O O O
11-05
S-curve Time Setting at
the Stop of Acceleration
0.00~2.50 0.20 s O O O
11-06
S-curve Time Setting at
the Start of Deceleration
0.00~2.50 0.20 s O O O
11-07
S-curve Time Setting at
the Stop of Deceleration
0.00~2.50 0.20 s O O O
11-08
Jump Frequency 1
0.0~599.0 0.0 Hz O O O
11-09
Jump Frequency 2
0.0~599.0 0.0 Hz O O O
11-10
Jump Frequency 3
0.0~599.0 0.0 Hz O O O
11-11
Jump Frequency Width
0.00 ~ 30.00 1.0 Hz O O O
11-12
Manual Energy Saving
Gain (V/F)
0~100 80 % O X X
11-14
OV Prevention Selection
230V:200V~400V
370
O X X
400V:400V~800V
740
11-17
Acceleration/Deceleration
Gain
0.1~10.0 1 O X X
11-18
Manual Energy Saving
Frequency
0.0~599.0
0.0 Hz O X X
11-28
Frequency Gain of Over
Voltage Prevention 2
1~200
100 % O X X
11-33
DC Voltage Filter Rise 0.1~10.0
0.1 Vdc O X X