4-39
Group 11 Auxiliary Parameters
Code Parameters Setting Range DefaultUnit
Control Mode
Attribute
V/F SLV
PM
SLV
Amount
11-34
DC Voltage Filter Fall
Amount
0.1~10.0
5.0 Vdc O X X *1
11-35
DC Voltage Filter
Deadband Level
0.0~99.0
10.0 Vdc O X X *1
11-36
Frequency gain of OV
Prevention
0.000~1.000
0.050 - O X X *1
11-37
Frequency limit of OV
Prevention
*0.00~599.00
5.00 Hz O X X *1
11-38
Deceleration start voltage
of OV prevention
200V: 200~400V 300
V O X X
400V: 400~800V 700
11-39
Deceleration end voltage
of OV Prevention
200V: 300~400V 350
V O X X
400V: 600~800V 750
11-40
OV Prevention Selection
0~3 0 O X X
11-47
KEB Deceleration Time
0.0~25.5 0.0 s O X X
11-48
KEB Detection Level
230V:190~210 200V
V O X X
400V:380~420 400V
11-55 STOP Key Selection
0:Stop Key is Disabled when the Operation
Command is not Provided by Operator.
1:Stop Key is Enabled when the Operation
Command is not Provided by Operator.
1 - O O O
11-59
Gain of Preventing
Oscillation
0.00~2.50 * O X X
11-60
Upper Limit of Preventing
Oscillation
0~100 * % O X X
11-61
Time Parameter of
Preventing Oscillation
0~100 0 O X X
11-62
Selection of Preventing
Oscillation
0:Mode 1
1:Mode 2
2:Mode 3
1 - O X X
11-63
Strong Magnetic
Selection
0:Disable
1:Enable
1 - X O X
11-69
Gain of Preventing
Oscillation 2
0.00~200.00 5.00 % O X X
11-70
Upper Limit of Preventing
Oscillation 2
0.01~100.00 5.00 % O X X
11-71
Time of Preventing
Oscillation 2
0~30000 100 ms O X X
11-72
Switch Frequency 1 of
Preventing Oscillation 2
0.01~300.00 30.00 Hz O X X
11-73
Switch Frequency 2 of
Preventing Oscillation 2
0.01~300.00 50.00 Hz O X X