4-43
Group 13 Maintance Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
13-00
Inverter Capacity
Selection
---- - - O O O *3*4
13-01
Software Version
0.00-9.99 - - O O O *3*4
13-02
Fault Record
0 - O O O *4
13-03
Cumulative
Operation Hours 1
0~23 - hr O O O *3*4
13-04
Cumulative
Operation Hours 2
0~65534 - day O O O *3*4
13-05
Selection of
Cumulative
Operation Time
0:Cumulative time in power on
1:Cumulative time in operation
0 - O O O *1
13-06
Parameters Locked
0:Parameters are read-only except 13-06 and
main frequency
1 : User defined parameters
2: All Parameters are Writable
2 - O O O
13-07
Parameter
Password Function
00000~65534 00000 - O O O
13-08
Restore Factory
Setting
1:2 wire initialization (50Hz) (220V/380V)
2:2 wire initialization (60Hz) (220V/380V)
3:2 wire initialization (50Hz) (230V/400V)
4:2 wire initialization (60Hz) (230V/460V)
5:2 wire initialization (50Hz) (220V/415V)
6:2 wire initialization (60Hz) (230V/400V)
7:2 wire initialization (50Hz) (220V/440V)
8:2 wire initialization (60Hz) (220V/440V)
9:2 wire initialization (60Hz) (220V/380V)
10:2 wire initialization (60Hz) (220V/380V)
1112:PLC initialization (RESET)
- - O O O
13-10
Situation
0~9999 - - O O O
13-51
Operation Time
Clearance Function
0:Do not clear operation time
1:Clear operation time
0 - O O O *1