4-47
Group 16 LCD Function Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
16-00
Main Screen
Monitoring
5~43
when using LCD to operate, the monitored item
displays in the first line. (default: frequency command)
16 - O O O *1*7
16-01
Sub-Screen
Monitoring 1
5~43
when using LCD to operate, the monitored item
displays in the second line. (default: output frequency)
17 - O O O *1*7
16-02
Sub-Screen
Monitoring 2
5~43
when using LCD to operate, the monitored item
displays in the third line. (default is output current))
18 - O O O *1*7
16-03 Display Unit
0~39999
Determine the display way and unit of frequency
command
0:Frequency display unit is 0.01Hz
1:Frequency display unit is 0.01%
2:Frequency display unit is RPM.
3~39:Reserved
40~9999:
Users specify the format, Input 0XXXX represents the
display of XXXX at 100%.
10001~19999:
Users specify the format; Input 1XXXX represents the
display of XXX.X at 100%.
20001~29999:
Users specify the format, Input 2XXXX represents the
display of XX.XX at 100%.
30001~39999:
Users specify the format, Input 3XXXX represents the
display of X.XXX at 100%.
0 - O O O *7
16-04
Engineering
Unit
0:No Unit
1:FPM
2:CFM
3:PSI
4:GPH
5:GPM
6:IN
7:FT
8:/s
9:/m
10:/h
11:°F
12:inW
13:HP
14:m/s
15:MPM
16:CMM
17:W
18:kW
19:m
20:°C
21:RPM
22:Bar
23:Pa
24:kPa
0 - O O O *7
16-05 LCD Backlight
0~7
5 - O O O *1*7
16-07
Copy Function
Selection
0:Do not copy parameters
1:Read inverter parameters and save
them to the operator.
2:Write the operator parameters to inverter.
3:Compare parameters of inverter and operator.
0 - O O O *7