4-53
Group 22 PM Motor Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
22-00
PM Motor Rated Power
0.00~600.00 KVA kW X X O
22-02
PM Motor Rated Current
25%~200% inverter rated current KVA A X X O
22-03
PM Motors Pole Number
2~96 8 Poles X X O
22-04
PM Motors
Rotation Speed
0~60000 1500 RPM X X O
22-05
PM Motors Maximum
Rotation Speed
0~60000 1500 RPM X X O
22-06
PM Motor Rated
Frequency
4.8~599.0 75.0 Hz X X O
22-10 PM SLV Start Current 20% ~ 200% Motor Rated Current 50 % X X O
22-11
I/F Mode Start Frequency
Switching Point
1.0 ~ 20.0 10.0 % X X O
22-14
Armature Resistance of
PM Motor
0.001 ~ 30.000 1.000 Ω X X O
22-15
D-axis Inductance of PM
Motor
0.01 ~300.00 10.00 mH X X O
22-16
Q-axis Inductance of PM
Motor
0.01 ~ 300.00 10.00 mH X X O
22-18
Flux-Weakening Limit
0~100 0 % X X O
22-21
PM Motor Tuning
0:PM Motor Tuning is not Active.
1:Parameter Auto-tune
0 - X X O
22-22
Fault History of PM Motor
Tuning
0:None
5:Loop Adjustment is Time Out
7:Other Errors of Motor Tuning
9:Current Abnormity Occurs when
Loop Adjustment
0 - X X O *4
22-23
PMSLV acceleration time
0.1~10.0
1.0 Sec X X O
22-25
Initial Position Detection
of PM Motor
0:Disable
1:Detected when inverter is running
1 - X X O