4-54
Group 23 PUMP & HVAC Function Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-00
Function Selection
0: Disable
1: PUMP
2: HVAC
3: Compressor
0 - O X X
23-01
Setting of Single &
Multiple Pumps and
Master & Slave
Machines
0: Single Pump
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
0 - O X X
23-02
Operation Pressure
Setting
0.10 ~ 650.00
2.00 PSI O X X
23-03
Maximum Pressure
Setting of Pressure
Transmitter
0.10 ~ 650.00
10.00 PSI O X X
23-04
Pump Pressure
Command Source
0:Set by 23-02
1:Set by AI
0 O X X
23-05
Display Mode
Selection
0: Display of Target and Pressure
Feedback
1: Target Pressure Only
2: Feedback Pressure Only
0 O X X
23-06
Proportion Gain(P) 0.00~10.00
3.00 - O X X
23-07
Integral Time(I) 0.0~100.0
0.5 Sec O X X
23-08
Differential Time(D) 0.00~10.00
0.00 Sec O X X
23-09
Tolerance Range of
Constant Pressure
0.01 ~ 650.00
0.5 PSI O X X
23-10
Sleep Frequency of
Constant Pressure
0.00 ~ 599.00
30.00 Hz O X X
23-11
Sleep Time of Constant
Pressure
0.0 ~ 255.5
0.0 Sec O X X
23-12
Maximun Presure Limit 0.00 ~ 650.00
5 PSI O X X
23-13
Warning Time of High
Pressure
0.0 ~ 600.0
10.0 Sec O X X
23-14
Stop Time of High
Pressure
0.0 ~ 600.0
20.0 Sec O X X
23-15
Minimum Pressure
Limit
0.00 ~ 650.00
5
%/P
SI
O X X
23-16
Warning Time of Low
Pressure
0.0 ~ 600.0
0.0 Sec O X X
23-17
Fault Stop Time of Low
Pressure
0.0 ~ 600.0
0.0 Sec O X X