4-55
Group 23 PUMP & HVAC Function Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-18
Time of Loss Pressure
Detection
0.0 ~ 600.0
0.0 Sec O X X
23-19
Proportion of Loss
Pressure Detection
0 ~ 100
0 % O X X
23-22
Slave Trip Frequency 0.00 ~ 599.00
45.00 Hz O X X
23-23
Direction of Water
Pressure Detection
0: Upward Detection
1: Downward Detection
1 - O X X
23-24
Range of Water
Pressure Detection
0.00 ~ 65.00
0.1 PSI O X X
23-25
Period of Water
Pressure Detection
0.0 ~ 200.0
30.0 Sec O X X
23-26
Acceleration Time of
Water Pressure
Detection
0.1 ~ 6000.0
KVA Sec O X X
23-27
Deceleration Time of
Water Pressure
Detection
0.1 ~ 6000.0
KVA Sec O X X
23-28
Forced Run Command 0.00 ~ 599.00
0.00 Hz O X X
23-29
Switching Time of
Water Pressure
Detection
0 ~ 240
3
Hr/
min
O X X
23-30
Detection Time of
Multiple Pumps in
Parallel Running Start
0.0 ~ 30.0
5.0 Sec O X X
23-31
Synchronous Selection
of Multiple Pumps in
Parallel
0: Disable
1: Pressure Setting Run/Stop
2: Pressure Setting
3: Run/Stop
1 O X X
23-34
Tolerance Range of
Constant Pressure 2
0.01 ~ 650.00
0.5 PSI O X X
23-35
Selection of Multiple
Pumps Shift Operation
0: No Function
1: Timer Alternately Selection
2: Sleep Stop Alternately Selection
3: Timer and Sleep Stop Alternately
Selection
4: Multiple Pumps Test Mode
1 O X X
23-37
Leakage Detection
Time
0.0~100.0
0.0 Sec O X X
23-38
Pressure Variation of
Leakage Detection
Restart
0.01 ~ 65.00
0.1 PSI O X X
23-39
Pressure Tolerance
Range of Leakage
Detection Restart
0.01 ~ 650.00
0.5 PSI O X X