4-56
Group 23 PUMP & HVAC Function Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
23-71
Maximum Pressure
Setting
0.10~650.00
10.00 PSI O X X
23-72
Switching Time of
Alternation in Parallel
0: Hour
1: Minute
0 O X X
23-73
Slave Wake-Up
Selection
0: Disable
1: Enable
0 O X X
23-74
High Pressure Setting
0: Disable
1: High Pressure Warning
2: High Pressure Warning or Error
2 O O O
23-75
Low Pressure Setting
0: Disable
1: Low Pressure Warning
2: Low Pressure Warning or Error
0 O O O
23-78
Selection of Loss
Pressure Detection
0: Disable
1: Loss Pressure Warning
2: Low Pressure Error
0 O O O