4-66
00- 07 Main and Alternative Frequency Command modes
Range
【0】:Main frequency
【1】:Main frequency + alternative frequency
When 00-07=0, the frequency source is set by the Main frequency parameter 00-05.
When 00-07=1, The frequency command will be the result of setting of main and alternative
frequencies. The inverter will display the SE01 error when 00-07=1 and parameter 00-05 and
00-06 are set to the same selection.
When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by
parameter 05-01 (Frequency setting of speed-stage 0).
00- 08 Communication frequency command
Range 【0.00~599.00】Hz
This parameter only can be used to read the set frequency in communication mode.
This parameter is only effective in the communication mode.
00- 09 Frequency Command save on power down
Range
【0】:Disable
【1】:Enable
This parameter is only enabled in communication mode
00- 10 Initial Frequency Selection of Stop
Range
【0】:By Current Frequency Command
【1】:By Zero Frequency Command
【2】:By Parameter 00-11
The parameter only can be used when main frequencysource comes from keypad.
When 00-10=0, the initial frequency is set by the current frequency.
When 00-10=1, the initial frrquency will be reset to 0.
When 00-10=2, the initial frequency will be set by 00-11.
00- 11 Initial Frequency Setpoint
Range 0.00-599.00
00-12 Frequency Upper limit
Range 【0.00-599.00】Hz
00-13 Frequency Lower limit
Range 【0.00-598.99】 Hz
Set the maximum frequency reference is 100% of the 01-02 or 01-16.
The inverter will display the SE01 error when 00-12 value is lower than 00-13. Frequency upper
and lower limit is active for all frequency reference modes.
When 00-13>0 and output frequency<00-13, inverter output frequency will be based on 00-13.