4-67
Figure 4.3.6 Frequency reference upper and lower limits
00-14 Acceleration time 1
Range 【0.1~6000.0】 Sec
00-15 Deceleration time 1
Range 【0.1~6000.0】 Sec
00-16 Acceleration time 2
Range 【0.1~6000.0】 Sec
00-17 Deceleration time 2
Range 【0.1~6000.0】 Sec
00-21 Acceleration time 3
Range 【0.1~6000.0】 Sec
00-22 Deceleration time 3
Range 【0.1~6000.0】 Sec
00-23 Acceleration time 4
Range 【0.1~6000.0】 Sec
00-24 Deceleration time 4
Range 【0.1~6000.0】 Sec
Preset Acceleration and Deceleration times set by above parameters.
Factory setting of acceleration timeis 00-14, factory setting of deceleration time is 00-15.
Acceleration time is the time required to accelerate from 0 to 100% of maximum output
frequency (01-02 or 01-16).
Deceleration time is the time required to decelerate from 100 to 0% of maximum output
frequency (01-02 or 01-16).
The default values for the accele. / decal. times are dependent on the inverter size.
Size
Acceleration / Deceleration
Default Value
200V series 400V series
1~10HP 1~15HP 10s
15~20HP 20~25HP 15s
30~40HP 30~75HP 20s
A. Select acceleration and deceleration time via the digital input terminals
The following table shows the acceleration / deceleration selected when the digital input function
Accel/ Decel time 1 is used.