4-68
Table 4.3.1 Acceleration/Deceleration Time Selection
Accel/decel time 1
(Set 03-00 to 03-05=10)
Acceleration
Time
Deceleration
Time
0 Taccc1(00-14) Tdec1(00-15)
1 Taccc2(00-16) Tdec2(00-17)
0 : OFF 1 : ON
Figure 4.3.7 Didital input S5 switch between Tacc1/Tacc2 and Tdec1/Tdec2
B. Switch of Acceleration/Deceleration time according to motors
03-00~03-06 set to 40 (Switching between motor 1/motor 2), it can switch motors by digital input.
(Motor 1 and Motor 2 selection function only for V/F control mode.)
When motor 1 selected, please refer table 4.3.1 for acceleration/deceleration time selection.
When motor 2 selected, please refer the table below of acceleration/deceleration time selection.
Motor 2 selected
Acceleration/Deceleratio
Selection
(Set 03-00 to 03-05 = 10)
Acceleration
Time
Deceleration
Time
0 Taccc3(00-21) Tdec3(00-22)
1 Taccc4(00-23) Tdec4(00-24)
00-18 Jog frequency
Range 【0.00~599.00】Hz
00-19 Jog acceleration time
Range 【0.1~600.0】Sec
00-20 Jog deceleration time
Range 【0.1~600.0】Sec
Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum
output frequency (01-02 or 01-16). Jog deceleration time (00-20) is the time required to
decelerate from 100 to 0% of maximum output frequency (01-02 or 01-16).
The JOG function is operational by using the multi-function input terminals S1 to S6 (00-02=1)
and setting the relevant parameters 03-00~03-05 to 6 or 7, the motor will run by the setting.
Refer to parameter group 3.