4-69
00- 26 Emergency stop time
Range
【0.1~6000.0】 Sec
When emergency stop input is activated the inverter will decelerate to a stop using the Emergency
stop time
When digital input set to 14, inverter will decelerate to stop by emergency stop time (00-26).
To cancel the emergency stop condition the run command has to be removed and emergency
stop input deactivated
Figure 4.3.9 Emergency stop example
00- 27 HD/ND Mode
Range
【0】: HD (Heavy Duty / Constant Torque)
【1】: ND (Normal Duty / Variable Torque)
The inverter overload curve, carrier frequency, stalls prevention level, rated input/output
current and maximum frequency are automatically set based on the inverter duty (HD/ND)
selection. Please refer to table 4.3.2 for detailed information.。
Table 4.3.2 Heavy Duty (Constant torque) / Normal Duty (Variable torque)
00-27
Overload
capacity
Carrier
frequency
Maximum
output
frequency
Stall
prevention
level
Rated input /
output
current
0
(H/D mode)
150%, 1min 2-16KHz 599.00Hz
150%
(08-00, 08-01)
Refer to
section 3.7
1
(N/D mode)
120%, 1min 2-16KHz 120.00Hz
120%
(08-00, 08-01)
Note:ND mode only can be used for 25-40HP of 200V class and 30-75HP of 400V class.
Select V/F curve (Group 1) and enter motor data (Group 2) to match the application.
In H/D mode, the maximum output frequency is 599Hz for all control modes, except for SLV
where the maximum output frequency is limited based on the inverter rating, see table below.