4-70
Horsepower Special circumtances
Maximum
output
frequency
220V 1~10HP, 440V 1~15HP - 150Hz
220V 15~20HP, 440V 20HP - 110Hz
440V 25HP - 100Hz
220V 25~40HP, 440V 30~75HP, 11-01 set to 8KHz(included) or below 100Hz
220V 25~40HP, 440V 30~75HP, 11-01 set to 8KHz or higher 80Hz
Note:In normal duty mode only applies to control modes V/F . All other modes must
use the Heavy Duty settings.
00- 34 Language
Range
【0】:English
【1】:Simplified Chinese
【2】:Traditional Chinese
【3】:Turkish
It is required to be with LCD keypad to display the language selection of parameter 00-34
00-34=0, LCD keypad displays in English.
00-34=1, LCD keypad displays in Simplified Chinese.
00-34=2, LCD keypad displays in Traditional Chinese.
00-34=3, LCD keypad displays in Turkish.
Note:It will not restore to the default value when this parameter performs initialization.
00- 35 Minumum Frequency Detection
Range
【0】:Alarm
【1】:Keep Running at Lower Frequency
00-35=0, when output frequency lower than minimum frequency (01-08), display will
show STP0 alarm.
00-35=1, when the frequency command is lower than minimum frequency, inverter will
keeping running at minimum frequency.
00- 36 PID Lower Frequency Selection
Range
【0】:Lower Frequency of PID Sleep Mode
【1】:0Hz of PID Sleep Mode
When 00-36=0, the lower frequency of PID sleep mode will base on 10-17~10-20.
When 00-36=1, the lower frequency of PID sleep mode is 0Hz.